CHAPTER 3
Advanced Functions
66
Enables analog port notifications if the analog value is higher
than limit for the given RTU and channel
NTF <dev> IOA..D 1..3 BELOW [limit]
Enables analog port notifications if the analog value is lower
than limit for the given RTU and channel
NTF <dev> IOA..D 1..3 OUTSIDE [lower-limit]
[upper-limit]
Enables analog port notifications if the analog value is outside
the limits for the given RTU and channel
NTF <dev> IOA..D 1..3 BETWEEN [lower-limit]
[upper-limit]
Enables analog port notifications if the analog value is between
the limits for the given RTU and channel.
R
ETURNS OK or error.
R
EMARKS The limit values must be given as physical values as configured in
the Configurator application, but without the physical unit, e.g.
37.0 for 37 degrees celsius.
Note: you can neither enable notifications for pulse counters
(cabling 4) nor for sensors that are not connected using the
Configurator application!
E
XAMPLES NTF 1234 IOA 5 OFF
Disables digital port notifications on IOA of RTU 1234
NTF 5678 IOC 5 ON
Enables digital port notifications on IOC of RTU 5678
NTF 1234 IOA 1 OFF
Disables analog notifications on IOA cabling 1 of RTU 1234
NTF 1234 IOA 2 ABOVE 70.0
Enables analog notifications if the physical value for IOA cabling 2
is above 70.0 (whatever physical unit the sensor has)
NTF 5678 IOC 3 OUTSIDE 12.0 34.0
Enables analog notifications if the physical value for IOC cabling 3
is outside the range of 12.0 to 34.0 (whatever physical unit the
sensor has)