Performing Advanced Functions
EXAMPLE For RSM
ANLG 0
9999 ANLG 0 5 5 5 5 5 5 5 5 4 4 5 5 0
#
For SSMAA (on channel 4)
ANLG 68
9999 ANLG 68 0
#
For DAN (on channel 0)
ANLG 160
9999 ANLG 160 0
#
For RNTTL (on channel 2)
ANLG 178
9999 ANLG 178 340 3900 0
#
For ENOPTR (on channel 10)
ANLG 202 1000
9999 ANLG 202 0
#
ANRT
AVAILABLE FOR
A731 A733A732 A733GSM
DESCRIPTION Sets/returns the routing of the hardware analog inputs to frame positions. This
command allows you to change the assignment of physical analog input ports to
data frame positions.
PARAMETERS None for inquiry. Position of value in frame and input channel for rerouting
operations.
R
ETURNS List of current routings.
R
EMARKS On inquiry the input channels are output in the order of their position within the data
frame (note: input channel numbers start with 0).
On changing the input channel routings, the first parameter specifies which data
frame position to use for the data value, and the second parameter determines
which input channel to use. The input channels on A733 and A733GSM/GPRS are
numbered from 0 to 11, but on A732 and A723 they are numbered from 0 to 5.
Input channels 0 to 2 are taken from I/O A, cabling 1 to 3; input channels 3 to 5 are
taken from I/O B, cabling 1 to 3; and so on. Two special input channels exist:
16 the value from the RTU’s internal temperature sensor (raw values
are in the range of 0 to 4095, which describe temperature values
from -68 to 332 degree Celsius)